East Kilbride

PrimarySPENSPT33 kV

At a glance

Sources retrieved 27 Sep 2026
Generation headroom
Not published
Demand headroom
Not published
Fault level
██.█kA
East Kilbride 33kV. SPD LTDS Appendix 4 Fault Levels (Table 4)
Firm capacity
Not published

Highest figure across the site's 2 busbars; fault level is the busbar nearest its break rating. Each busbar is listed below.

Location

55.78534, -4.19330

From DNO data
Directions (Google Maps, new tab)

Connection queue

SPEN Embedded Capacity Register (>1 MW), retrieved 27 Sep 2026

Queued
██.█MW
Connected
██.█MW
Projects
14
Unlock the full 14-project queue with a premium subscription

33 kV

1 busbar

East Kilbride 33kV

SPENdistribution Source (opens the operator's dataset in a new tab)
Fault level (3-phase)
██.█kA
SPD LTDS Appendix 4 Fault Levels (Table 4)

Not published for this busbar: generation headroom, demand headroom, firm capacity.

Fault and rating detail
Fault level (1-phase)
██.█kA
Make rating
██.█kA
Break rating
██.█kA

Other voltage levels

  • Voltage not statedEast Kilbride SPTNot openly published by NESO

Planned reinforcement

1 schemeDNO Network Development Reports
SchemeDriverUpliftIn service
SPT will install a three-panel switchboard onto cabling between each SGT and 33kV incomer on the East Kilbride switchboard. A 30MVA reactor will be connected between each three-panel switchboard to provide an alternative path when the bus-section circuit breaker on the main switchboard is operated in the normally open position, thereby limiting the fault level infeed from the transmission system.Fault Level

Data source

Distribution operator: SP Energy Networks. Licence: CC BY 4.0

Transmission owner: Scottish Power Transmission. Licence: CC BY 4.0

Derived from publicly available DNO and TSO datasets: we cluster, merge and calculate from the published records, so these figures are modified from the source. Indicative only; verify directly with the operators before making connection decisions. Attribution and licences