East Kilbride 33kV
SPENdistribution Source (opens the operator's dataset in a new tab)Not published for this busbar: generation headroom, demand headroom, firm capacity.
Highest figure across the site's 2 busbars; fault level is the busbar nearest its break rating. Each busbar is listed below.
SPEN Embedded Capacity Register (>1 MW), retrieved 27 Sep 2026
Not published for this busbar: generation headroom, demand headroom, firm capacity.
| Scheme | Driver | Uplift | In service |
|---|---|---|---|
| SPT will install a three-panel switchboard onto cabling between each SGT and 33kV incomer on the East Kilbride switchboard. A 30MVA reactor will be connected between each three-panel switchboard to provide an alternative path when the bus-section circuit breaker on the main switchboard is operated in the normally open position, thereby limiting the fault level infeed from the transmission system. | Fault Level |
Distribution operator: SP Energy Networks. Licence: CC BY 4.0
Transmission owner: Scottish Power Transmission. Licence: CC BY 4.0