YATTON KEYNELL 11 kV
Network Hierarchy
CurrentYATTON KEYNELL 11 kV
BSPCHIPPENHAM
GSPMELKSHAM
Headroom may be constrained by upstream infrastructure (BSP/GSP)
Network Constraints
Constraint Details
- Upstream constrained
- Subject to Mod App outcome Reinforce the 33kV circuit between Chippenham BSP and Yatton Keynell (Mar 2027) Replace the 33kV switchgear at Chippenham BSP (Aug 2027) Reinforce the 132kV circuits between Melksham GSP and Chippenham (Aug 2027) Add a 3rd 90MVA BSP transformer at Chippenham (Oct 2027) Add a new 33kV circuit between Yatton Keynell and Alterton (Jun 2028)
- Distribution constrained
- Replace the existing transformers with 7.5MVA units
- Constrained due to upstream thermal limitations on Chippenham BSP TX under N-1
- Upstream queue: 515.5MW
Upstream TX Queue N/A
contracted generationat upstream GSP
High queue indicates significant generation already contracted at this connection point.